Installing and Connecting the Basic System
S5-95F
How to Set the Subunit Identifier
Set the subunit identifier on both subunits.
One subunit is assigned identifier "A", the other identifier "B".
Figure 4-6. Setting the Subunit Identifiers
Subunit A
Subunit B
You should observe that by setting the subunit identifers you also define the addressing and wiring
rules for the I/Os.
How to Set the Length of the Fiber Optic Cable
Use the lower three switches to set the length of the fiber optic cable. The fiber optic cable can
be 1, 2, 5 or 10 m long (3.28, 6.56, 16.4 or 32.8 ft).
Figure 4-7. Setting the Length of the Fiber Optic Cable
1 m (3.28 ft)
2 m (6.56 ft)
5 m (16.4 ft)
10 m (32.8 ft)
How to Connect the Fiber Optic Cable
Connect the two basic units via the fiber optic cable.
Note
Observe the following when connecting the fiber optic cable:
•
Make sure that the connectors are not contaminated by dust, grease, etc., as this
causes impermissible damping.
•
The bending radii for fiber optic cables must at least be 40 mm.
4-6