Module Spectrum
S5-95F
Analog Input Module 4 x±10 V (continued)
(6ES5 464-8MC11)
Technical Specifications
Input ranges
(rated values)
±10 V
Number of inputs
1, 2 or 4
(selectable)
Galvanic isolation
yes (inputs to
grounding point;
not between inputs)
Input resistance
50 k
Connection method
two-wire
of sensors
connection
Digital representation
12 bits+sign
of input signal
(2048 units =rated
value)
Measured value
two's complement
representation
(left-justified)
Measuring principle
integrating
Conversion principle
voltage-time
conversion
(dual slope)
Integration time
20 ms at 50 Hz
(adjustable for optimum
16.6 ms at 60 Hz
noise suppression)
Encoding time
per input
- for 2048 units
max.
60 ms at 50 Hz
max.
50 ms at 60 Hz
- for 4095 units
max.
80 ms at 50 Hz
max.
66.6 ms at 60 Hz
Permissible voltage
difference
- between inputs
max.
±1 V
- between inputs and
central ground point
max.
75 V DC/60 V AC
Permissible
input voltage
(destruction limit)
max.
50 V DC
Fault indication for
- range exceeded
yes (more than
4095 units)
- sensor wire break
no
- general indication of
wire break
no
Noise suppression
for f=nx
(50/60 Hz±1%);
n=1,2, ...
- common-mode
min.
86 dB
rejection (V
pp
=1 V)
- series-mode rejection
min.
40 dB
(peak value of noise
< rated value of
input range)
Basic error limits
±0.2 %
(operational error limits
at 25°C (77 °F), referred to the
input ranges of the module)
Operational error limits
±0.45 %
(0 to 60 °C (32 to 140 °F),
referred to the input
ranges of the module)
Length of cable
- shielded
max.
200 m (660 ft.)
Supply voltage L+
none
Rated insulation voltage
(+9 V to )
12 V AC
- insulation group
1×B
- tested with
500 V AC
Rated insulation voltage
(inputs to +9 V)
60 V AC
- insulation group
1×B
- tested with
500 V AC
Current consumption
- from +9 V (CPU)
typ.
70 mA
Power loss of the
module
typ.
0.7 W
Weight
approx.
230 g (8 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2
Severity rating: none
tested with
4 kV air discharge
<2 kV contact
discharge
Electromagnetic fields
to IEC 801-3
Severity rating 2
tested with
3 V / m
Fast transient burst
to IEC 801-4
Severity rating 3
tested with
1 kV on signal lines
A-20
EWA 4NEB 812 6210-02