8-10
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
8.2.3
Structure of Diagnosis
The structure of the diagnostic message conforms with the PROFIBUS-DP
standard.
Note
The structure of the diagnostic message described below does not apply to a
default start-up (refer to section 8.2.9).
The diagnostic message for the IM308C contains 26 bytes of data. The struc-
ture of the complete diagnosis is shown in Table 8-6.
Table 8-6
Structure of diagnostic message
Byte(s)
Contents
0
Station status 1
1
Station status 2
2
Station status 3
3
Station number, DP master
4
Manufacturer ID (801B
H
)
5
6
Header and length of module diagnosis
7
Module diagnosis
8
Header and length of first station diagnosis
9
Length of S7 area
10
Reserved
11
Reserved
12 – 15
Part 1 of diagnostic data
16
Length of second station diagnosis (ASi-specific part)
17
Length of S7 area
18
Reserved
19
Reserved
20 – 25
Part 2 of diagnostic data.
Introduction
Structure for
IM 308C
Diagnostics and Error Handling
Содержание SIMATIC Distributed I/O System DP/ASi Link
Страница 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Страница 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Страница 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Страница 60: ...4 24 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Installing and Wiring the DP ASi Link ...
Страница 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Страница 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Страница 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Страница 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...