![Siemens SIMATIC Distributed I/O System DP/ASi Link Скачать руководство пользователя страница 126](http://html.mh-extra.com/html/siemens/simatic-distributed-i-o-system-dp-asi-link/simatic-distributed-i-o-system-dp-asi-link_manual_382813126.webp)
C-10
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
C.4
Structure of the Parameterization Message in Simple Configuration
The parameterization message has a fixed length of exactly 32 bytes.
Bytes 0 to 6 contain the parameters of the DP standard part.
Table C-8
Assigning the DP standard part
Byte
0
1
2
3
4
5
6
Value
Refer to Table C-1
Bytes 7 to 14 are referred to as the initialization bytes.
The structure of the first initialization byte, byte 7, is described in Table C-3.
Bytes 8 to 14 contain fixed default values for initialization of the DP/ASi
link, which must not be modified.
Table C-9
Default values of bytes 8 to 14 for initialization
Byte
8
9
10
11
12
13
14
Value
00
H
00
H
16
H
51
H
04
H
8A
H
11
H
Byte 15 defines the response when the actual configuration read by the DP/
ASi link does not agree with the setpoint configuration.
Table C-10
Definition of response when setpoint and actual configurations differ
Byte
15
Value
Refer to Table C-5
Parameterization
message structure
DP standard part
Initialization bytes
Control byte
Parameterization Message
Содержание SIMATIC Distributed I/O System DP/ASi Link
Страница 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Страница 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Страница 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Страница 60: ...4 24 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Installing and Wiring the DP ASi Link ...
Страница 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Страница 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Страница 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Страница 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...