3-10
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
Both the 2-core cable and the 5-core cable can be connected to the program-
mer connector.
A programmer connector may be placed anywhere on the PROFIBUS-DP
field bus. When doing so, pay attention to the following:
Since a terminating resistor cannot be inserted, the programmer connector
must not be located at the ends of the bus line.
You may place several programmer connectors on the bus. However, you
may connect only one programmer to one of the programmer connectors
on the bus, since the programmer represents a node having the station
number 0.
For connecting a programmer, the following values apply to the length of
the spur line as a function of the baud rate on the PROFIBUS-DP bus:
Table 3-3
Length of the spur line of the programmer connection as a function of
the baud rate on the PROFIBUS-DP bus
Baud Rate
Max. Length of Spur Line
< 500 kBd
Max. 32
3 m
Max. 10
5 m
Max. 1
10 m
1500 kBd
Max. 5
2 m
(3 m spacing)
or
PROFIBUS bus terminal
> 1500 kBd
Max. 1
1.5 m
Rule for
connection of
programmer
connector
Configuration Options
Содержание SIMATIC Distributed I/O System DP/ASi Link
Страница 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Страница 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Страница 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Страница 60: ...4 24 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Installing and Wiring the DP ASi Link ...
Страница 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Страница 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Страница 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Страница 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...