D-5
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
The following example presents the structure of the five bytes of data (bytes
15 to 19) for a DP/ASi link with inputs and outputs.
Byte
Value
Meaning
15
C2
H
Specific identification format:
there follows one length byte for output data
there follows one length byte for input data
there follow two bytes of manufacturer-specific data
16
00
H
Length byte for output data:
data format: byte
byte consistency
output length: 1 byte
17
01
H
Length byte for input data:
data format: byte
byte consistency
input length: 2 bytes
18
3C
H
Manufacturer-specific data
19
40
H
The following example shows the structure of the five bytes of data (bytes 15
to 19) for a DP/ASi link having only inputs.
Byte
Value
Meaning
15
43
H
Specific identification format:
there follows one length byte for input data
no output data are present
there follow three bytes of manufacturer-specific iden-
tification
16
02
H
Length byte for input data:
data format: byte
byte consistency
input length: 3 bytes
17
00
H
Manufacturer-specific data
18
3C
H
19
40
H
Example 1
Example 2
Configuration Message
Содержание SIMATIC Distributed I/O System DP/ASi Link
Страница 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Страница 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Страница 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Страница 60: ...4 24 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Installing and Wiring the DP ASi Link ...
Страница 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Страница 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Страница 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Страница 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...