![Siemens SIMATIC Distributed I/O System DP/ASi Link Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/siemens/simatic-distributed-i-o-system-dp-asi-link/simatic-distributed-i-o-system-dp-asi-link_manual_382813053.webp)
4-17
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
4.4.2
Power Supply Connector (6ES5 762-2CS11)
The power supply connector is used to link the PROFIBUS-DP and the 24
VDC external power supply for the DP/ASi link.
The power supply connector has the following characteristics:
Degree of protection: IP 66/IP 67 (refer to installation rules, section 4.1)
Can be operated at the following baud rates
9.6; 19.2; 93.75; 187.5; 500; 1500; 3000; 6000 and 12000 kBd
The 3000, 6000 and 12000 kBd baud rates are possible only in the case of
operation with a suitable DP master – for example, the IM 308-C.
Can be loaded with up to 4 A input power. This limits the number of mod-
ules that can be connected (refer to section 3.4)
Is not a bus station having a station number.
Is secured without opening the cover.
The power supply connector has the following connections:
Connection for an ”incoming” PROFIBUS-DP (12-pin socket)
Connection for an ”incoming” external power supply
(6-pin connector)
Connection for an ”outgoing” PROFIBUS-DP with power supply (12-pin
socket)
Grounding screw for connecting PI
Usage
Characteristics
Connections
Installing and Wiring the DP/ASi Link
Содержание SIMATIC Distributed I/O System DP/ASi Link
Страница 6: ...vi Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Preface ...
Страница 18: ...1 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Overview ...
Страница 26: ...2 8 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b ASi Basics ...
Страница 60: ...4 24 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Installing and Wiring the DP ASi Link ...
Страница 72: ...5 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Configuring the DP ASi Link ...
Страница 116: ...B 2 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b I O Code ...
Страница 128: ...C 12 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Parameterization Message ...
Страница 148: ...Index 6 Distributed I O System DP ASi Link EWA 4NEB 710 6055 02b Index ...