4. Select the shortcut menu command Object Properties ... .
5. Open the "General" tab.
– Enter the system-specific device name for this CFU.
– Select the following check boxes in the "Node in PROFINET IO system" area:
- Check box "Assign IP address via IO Controller"
- Check box "Configuration with PDM"
You can also specify the address manually.
6. If the Maintenance Station is used or recommendation:
Open the "Identification" tab. Enter the system-specific data.
Selecting the BusAdapter
An RJ45 bus adapter is inserted by default.
1. Select the BusAdapter to be replaced in the CFU.
2. In the current PCS 7 profile open the following folder:
PROFINET IO > I/O > Compact Field Unit > Compact Field Unit (Variant) > BusAdapter >
<"Type of BusAdapter">.
3. Double-click the type of the required BusAdapter.
The BusAdapter is inserted at both ports of the CFU.
The BusAdapter type can be swapped for the selected CFU. To do so click the required
BusAdapter in the hardware catalog.
Note
Note on downloading
The following conditions must be met for the CFU:
● The device name of the CFU (online) must match the device name from the configuration.
● The article number of the configured CFU must be identical to the article number of the CFU
present in the system.
● The firmware version of the configured CFU must not be higher than the firmware version
of the CFU present in the system.
Additional information
● Section "Configuring a freely configurable channel (DIQ) (Page 85)"
● Section "CFU PA: Configuring a PROFIBUS PA field device (offline) (Page 88)"
8.8.2.3
Configuring a freely configurable channel (DIQ)
In the following configuration the CFU is shown, as an example, with configured channels at a
redundant IO Controller.
Commissioning
8.8 Commissioning (offline)
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
85
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...