IB 6 / IB 11
Action
Meaning
xx1x xxx
STS_M_INTER‐
VAL_<x>
Only in "Frequency measurement" operating mode (channels 0 and 1)
Status of the frequency value: (0 = frequency value is invalid; 1 = frequency value is
valid)
xxx1 xxx
STS_SW_GATE_
<x>
Status of the SW_GATE mirrored
xxxx xx1x
STS_GATE_<x>
Status of the internal gate (0 = gate closed, 1 = gate open), depending on the SW and
HW gate, when the HW gate is activated.
xxxx xxx1
STS_DQ_<x>
Logic for the comparison event DQ from the parameters
Output area
The table shows the allocation of the address space of the control interface.
Table A-18
Address space of the CFU DIQ with submodule "DIQ16 DC24V/0.5A, Counter"
QB x +
7
6
5
4
3
2
1
0
0
DQ7
DQ6
DQ5
DQ4
DQ3
DQ2
DQ1
DQ0
1
DQ15
DQ14
DQ13
DQ12
DQ11
DQ10
DQ9
DQ8
2
Load value 0
3
4
5
6
-
-
-
-
SW_GATE_
0
LD_SLOT_0
7
Load value 1
8
9
10
11
-
-
-
-
SW_GATE_
1
LD_SLOT_1
QB 6 / QB 11
Action
Meaning
xxxx 0000
STOP (SW_GATE=0)
Stop counting
xxxx 0001
Apply load value; STOP (SW_GATE=0)
The load value is applied with a rising edge of bit 0 when
the counter is stopped
xxxx 1001
Apply load value; START (SW_GATE=1)
The load value is applied with a rising edge of bit 0;
counting continues
xxxx x000
NOP
No action
xxxx x001
Counter = load value
Load load value into the counter as the count value
Appendix
A.9 Drivers, parameters, diagnostic messages and address space
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
199
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...