Ordinary locations
● UL 61010-2-201; First Edition, Dated January 24, 2014; IEC 61010-2-201:2017
(Note: This standard is supplemented by UL 61010-1, Third Edition, Dated May 11, 2012)
● CSA C22.2 No. 142 (Process Control Equipment)
Hazardous locations
● ISA 12.12.01
● CSA C22.2 No. 213
APPROVED for use in
Class I, Division 2, Group A, B, C, D Tx;
Class I, Zone 2, Group IIC Tx
Note the following information:
Note
This product must be installed according to the NEC (National Electric Code) stipulations.
When used in environments according to class I, division 2 (see above), the CFU must be
mounted in an enclosure that corresponds to at least IP54 according to EN 60529.
Installation instructions according to cULus
WARNING
Installation instructions according to cULus
WARNING – Explosion Hazard - Do not connect or disconnect the device while circuit is live
unless area is known to be non-hazardous.
WARNING – Explosion Hazard - Substitution of components may impair suitability for Class
I, Division 2 or Class I, Zone 2.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C or D; Class I, Zone 2,
Group IIC, or non-hazardous locations only.
12.1.1.6
FM Approval
Table 12-3
Factory Mutual Research (FM) Certification
Classification
NI, Class I, Div 2, Groups A, B, C, D Tx;
NI, Class I, Zone 2, Groups IIC Tx
Standards
Class No. 3600
Class No. 3611
Class No. 3810
Technical specifications
12.1 General technical specifications
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
151
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...