Article number
6ES7655-5PX31-1XX0
Cable length
● shielded, max.
1 000 m
● unshielded, max.
600 m
Digital outputs
Type of digital output
Transistor
Number of digital outputs
16
Current-sinking
No
Current-sourcing
Yes
Short-circuit protection
Yes
● Response threshold, typ.
0.7 to 1.3 A
Limitation of inductive shutdown voltage to
Typ. L+ (-50 V)
Controlling a digital input
Yes
Switching capacity of the outputs
● on lamp load, max.
5 W
Load resistance range
● lower limit
48 Ω
● upper limit
12 kΩ
Output voltage
● Type of output voltage
DC
● for signal "1", min.
Ue minus 1 V
Output current
● for signal "1" rated value
0.5 A
● for signal "0" residual current, max.
0.1 mA
Output delay with resistive load
● "0" to "1", max.
50 µs
● "1" to "0", max.
100 µs
Parallel switching of two outputs
● for uprating
No
● for redundant control of a load
No
Switching frequency
● with resistive load, max.
100 Hz
● with inductive load, max.
2 Hz
● on lamp load, max.
10 Hz
Total current of the outputs
● Current per channel, max.
0.5 A
horizontal installation
– up to 60 °C, max.
5 A
– up to 70 °C, max.
4 A
vertical installation
– up to 60 °C, max.
5 A
Cable length
● shielded, max.
1 000 m
Technical specifications
12.4 Technical specifications of the Compact Field Unit DIQ
SIMATIC CFU
176
Commissioning Manual, 08/2019, A5E39252870-AD
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...