Rule for ...
Connections PS<n>
Connections FB<n> and DIQ<n>
Permitted cable
cross-sections for
flexible cables
Without ferrule
0.2 to 2.5 mm
2
AWG
*
: 24 to 13
AWG*: 24 to 14
With ferrule (with plastic sleeve)
***
0.25 mm to 1.5 mm
2**
0.14 mm to 1.5 mm
2
AWG
*
: 24 to 16
AWG
*
: 26 to 16
With TWIN ferrule
***
0.5 mm to 1 mm
2
0.5 to 0.75 mm
2
(see below)
AWG
*
: 20 to 17
AWG
*
: 20 to 18
Stripped length of the cables
7 to 10 mm
Wire end ferrules in accordance with DIN 46228 with
plastic sleeve
***
7 and 10 mm long
* AWG: American Wire Gauge
** Ferrules without plastic sleeve: 0.25 to 2.5 mm
2
/AWG: 24 to 13
*** See note on ferrules
Note
Ferrules
You can achieve optimum results with respect to a high-quality and durable electrical
connection with maximum conductor extraction forces through the use of crimp shapes,
preferably with smooth surfaces, as is ensured for example with rectangular and trapezoidal
crimp cross-sections.
Due to the variety of crimp shapes used in industry, we recommend other shapes on request.
Crimping dies with a pronounced wave profile are unsuitable.
A.5
Dimensional diagrams
A.5.1
Dimension drawings of the mounting rails
Dimensions for the drill holes
Mounting rails can be ordered in the lengths 483 mm and 2000 mm.
Appendix
A.5 Dimensional diagrams
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
187
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...