3. Wait until the field bus LED lights up in static green: The new field device is ready for
operation.
4. Reload the system-specific field device parameters using SIMATIC PDM.
Replacing a field device (different manufacturer and same type (when using profiles))
1. Disconnect the field device to be replaced.
2. Connect the new field device.
3. Wait until the field bus LED lights up in static green: The new field device is ready for
operation.
4. In the HW Config, assign the correct EDD to the field device. To do this, select the SIMATIC
PDM > Device Selection (Reassign) ... menu command in the shortcut menu.
5. Reload the system-specific field device parameters using SIMATIC PDM.
Replacing a field device (different type)
1. Remove the field device from the configuration in HW Config.
2. Download the configuration.
3. Connect the new field device to the CFU PA.
4. Reassign parameters of the fieldbus connection of the CFU PA (FIELDBUS; FB<n>).
You can find information on this in section "CFU PA: Configuring a PROFIBUS PA field
5. Download the configuration.
6. Reload the system-specific field device parameters using SIMATIC PDM.
Additional information
You can find information on the tightening torques in section "Tools and tightening torques
(Page 186)".
10.10
CFU PA: Adding field devices
CFU PA in hazardous area
If you are using the CFU in a hazardous area, you must observe the following sections:
● Section "Use in hazardous areas (Page 29)"
● Section "Compact Field Unit in the housing for use in a hazardous area (Page 129)"
Servicing and maintenance
10.10 CFU PA: Adding field devices
SIMATIC CFU
122
Commissioning Manual, 08/2019, A5E39252870-AD
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...