Additional information
● You can find information about required tools in section "Tools and tightening torques
● You can find information about cables and wire end ferrules in section "Preparing cables
7.3
Connecting the power supply to the CFU
Introduction
The power supply of the CFU is fed via two 2-pole connection plugs that are capable of feed-
through wiring and are located on the front of the CFU.
You can find information on power consumption for the CFU version used in section "Technical
specifications (Page 147)".
Power supply unit
WARNING
Safety extra-low voltage
Only use power supply units of type SELV/PELV with safe electrically isolated functional extra
low voltage (≤ 28.8 V DC).
For the CFU PA, the SELV/PELV power supply unit must also comply with at least one of the
following requirements:
● The power supply unit supplies safety extra low voltage (SELV) with power limitation
(Limited Power Source, LPS) in accordance with the following standards: IEC 60950-1 /
EN 60950-1 / VDE 0805-1.
● The power supply unit for the device complies with NEC Class 2 of the National Electrical
Code (r) (ANSI / NFPA 70).
NOTICE
Potentials
The freely configurable channels of the CFU are connected to the potentials of the power
supplies (not floating).
● CFU PA: In case of polarity reversal of the power supply, a short circuit is possible via the
ground connections.
● CFU DIQ: The power supply connections are protected against polarity reversal.
Observe section "Use in hazardous areas (Page 29)", if necessary.
Connecting
7.3 Connecting the power supply to the CFU
SIMATIC CFU
56
Commissioning Manual, 08/2019, A5E39252870-AD
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...