7.4.2
Connecting a sensor / actuator to the CFU
Read section "Use in hazardous areas (Page 29)" if needed.
The CFU offers freely configurable channels (DIQ; DIQ<n>). You can connect a sensor or an
actuator to each freely configurable channel of the CFU.
● You can find information on the terminal pin assignment in the following sections:
– Section "CFU PA: Terminal assignment (Page 183)"
– Section "CFU DIQ: Terminal assignment (Page 184)"
● You can find information on the tightening torques in section "Tools and tightening torques
(Page 186)".
Terminals for the freely configurable channels (DIQ<n> for one sensor or actuator each)
Plug with screw-type terminals
Plug with push-in terminals
',4
',4
',4
',4
',4
',4
',4
',4
',4
',4
',4
',4
',4
',4
',4
',4
Wiring
CAUTION
Current carrying capacity of the CFU
Observe the total maximum permissible load current of all channels together (total current Us
+DQ) and temperature-dependent limits.
You can find information about this in section "Rules for the operation (Page 23)".
Parallel connection not permitted
● Parallel connection of sensor supplies is not permitted.
● Parallel connection of digital outputs is not permitted.
Sensor supply
● An external power supply as DI sensor supply is not permitted. This error is recognized by
the CFU during run-up or during re-parameterization and triggers a diagnostic interrupt. All
freely configurable channels are disabled until the error has been remedied.
You can find additional information in the following sections:
● Section "Technical specifications of the Compact Field Unit PA (Page 165)"
● Section "Configuring freely configurable channels (parameter overview - DIQ) (Page 94)"
Connecting
7.4 Connecting the device to the CFU (PROFIBUS PA field device, sensor, actuator)
SIMATIC CFU
60
Commissioning Manual, 08/2019, A5E39252870-AD
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...