10.7
Replacing / modifying a sensor / actuator
NOTICE
Replacing sensors/actuators during process operation (AS in RUN)
Interrupt OBs must be configured in the automation system so that sensors/actuators can be
replaced during process operation (implemented as a standard feature in PCS 7).
Read section "Use in hazardous areas (Page 29)" if needed.
Preparation
1. Before replacement (in HW Config), disable the sensor/actuator.
2. Download the parameters to the CFU.
The sensor/actuator is current-free.
Replacing a sensor/actuator (with one of the same type)
1. Connect the new sensor/actuator to the CFU.
The new sensor/actuator is ready for operation.
Once the new sensor/actuator is connected, you can enable the sensors/actuators again.
Replacing a sensor/actuator (with one of a different type)
1. Reassign the parameters of the channel (DIQ<n>)
You can find additional information in section "Configuring freely configurable channels
(parameter overview - DIQ) (Page 94)".
2. Ensure that the configured sensor/actuator is connected to the CFU.
3. Download the parameters to the CFU.
4. Enable the sensor/actuator (in HW Config).
Additional information
Section "Tools and tightening torques (Page 186)"
10.8
Overload of freely configurable channels (DIQ<n>)
At a thermal overload, all configurable channels of the CFU are disabled.
Servicing and maintenance
10.8 Overload of freely configurable channels (DIQ<n>)
SIMATIC CFU
120
Commissioning Manual, 08/2019, A5E39252870-AD
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...