Article number
6ES7655-5PX31-1XX0
Short-circuit protection
Yes; Electronic
Output current
● up to 60 °C, max.
5 A
● up to 70 °C, max.
4 A
Power loss
Power loss, typ.
2.88 W; Depending on the type of BusAdapter
used (typ. RJ45)
Address area
Address space per station
● Address space per station, max.
1 440 byte; Dependent on configuration
Digital inputs
Number of digital inputs
16
Source/sink input
Yes; P-reading
Input characteristic curve in accordance with
IEC 61131, type 1
Yes
Input characteristic curve in accordance with
IEC 61131, type 2
No
Input characteristic curve in accordance with
IEC 61131, type 3
Yes
Pulse extension
No
Number of simultaneously controllable inputs
horizontal installation
– up to 60 °C, max.
16; Total current must be observed, see DQ
– up to 70 °C, max.
16; Total current must be observed, see DQ
vertical installation
– up to 60 °C, max.
16; Total current must be observed, see DQ
Digital input functions, parameterizable
● Counter
Yes
– Number, max.
2
– Counting frequency, max.
1 kHz
– Counting width
32 bit
– Counting direction up/down
Yes; Up
Input voltage
● Rated value (DC)
24 V
● for signal "0"
-30 to +5V
● for signal "1"
+11 to +30V
Input current
● for signal "1", typ.
2.5 mA; Typical
Input delay (for rated value of input voltage)
for standard inputs
– parameterizable
No
– at "0" to "1", max.
3.2 ms; for counter function 0,1 ms
– at "1" to "0", max.
3.2 ms; for counter function 0,1 ms
Technical specifications
12.4 Technical specifications of the Compact Field Unit DIQ
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
175
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...