6-3
C7-621 / C7-621 AS-i Control Systems
C79000-G7076-C621-01
The following table shows the technical data of the digital inputs of the C7
CPU.
Module-Specific Data
Number of inputs
16
Cable length
S
Unshielded
max. 600 m
Voltages, Currents, Potentials
Rated load voltage L+
S
Re verse polarity
protection
DC 24 V
yes
Number of simultaneously
accessible inputs
16
Floating
no
Status, Interrupt, Diagnostics
Interrupts
no
Diagnostic functions
no
Data for Selecting a Sensor
Input voltage
S
Rated value
S
For signal “1”
S
For signal“0”
DC 24 V
11 to 30 V
-3 to +5 V
Input current
S
For signal “1”
Typically 7 mA
Input delay
S
From “0” to “1”
S
From “1” to “0”
1.2 to 4.8 ms
1.2 to 4.8 ms
Input characteristics
Complying with IEC
1131, Type 2
Connection of 2-wire BEROs
S
Permitted closed-circuit
current
Possible
max. 2 mA
Digital Input
C7-621 Digital I/Os
Содержание simatic c7-621
Страница 44: ...2 26 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Installing and Preparing the C7 ...
Страница 64: ...3 20 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Configuring an MPI Network ...
Страница 74: ...5 4 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Attaching a C7 621 AS i ...
Страница 82: ...6 8 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 C7 621 Digital I Os ...
Страница 100: ...7 18 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 C7 621 Analog I Os ...
Страница 101: ...8 1 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Maintenance 8 ...
Страница 110: ...A 8 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 General Technical Specifications ...
Страница 123: ...Glossary 1 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Glossary ...
Страница 136: ...Index 4 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Index ...