3-19
C7-621 / C7-621 AS-i Control Systems
C79000-G7076-C621-01
3.5.4
Connecting the Bus Connector to a Module
To connect the bus connector, follow the steps outlined below:
1. Plug the bus connector into the module.
2. Screw the bus connector securely to the module.
3. If the bus connector with the order number 6ES7 ... is located at the start
or end of a segment, you must activate the terminating resistor (switch
setting “ON”) (see Figure 3-14 ).
Note
The bus connector 6ES7 972-0BA30-0XA0 does not have a terminating
resistor. You cannot plug in this bus connector at the start or end of a
segment.
Make sure that the stations on which the terminating resistor is located are
always turned on during startup and operation.
Terminating
resistor on
Terminating resistor
off
on
off
on
off
Figure 3-14
Bus Connector (6ES7 ... ): Terminating Resistor Activated and
Deactivated
You can remove the bus connector with a LAN cable connected through at
any time from the PROFIBUS DP interface without interrupting the data
exchange on the bus.
!
Warning
Disturbance of data exchange on the bus is possible!
A bus segment must always be terminated at both ends. This is, for example,
not the case if the power supply to the last slave with a bus connector is not
turned on. Since the bus connector takes its power from the station, this
would make the terminating resistor ineffective.
Make sure that the stations on which the terminating resistor is activated, are
always turned on.
Connecting the
Bus Connector
Removing the Bus
Connector
Configuring an MPI Network
Содержание simatic c7-621
Страница 44: ...2 26 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Installing and Preparing the C7 ...
Страница 64: ...3 20 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Configuring an MPI Network ...
Страница 74: ...5 4 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Attaching a C7 621 AS i ...
Страница 82: ...6 8 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 C7 621 Digital I Os ...
Страница 100: ...7 18 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 C7 621 Analog I Os ...
Страница 101: ...8 1 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Maintenance 8 ...
Страница 110: ...A 8 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 General Technical Specifications ...
Страница 123: ...Glossary 1 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Glossary ...