Integration into the User Program
4-32
C7-613 Control System
A5E00138934-03
Structure and Description
Table 4-9
Structure of the Event Buffer DB
Address
Name
Type
Description
0
EVENT[1].NUMBER
BYTE
Message number
The first message is the most recent
message
1
EVENT[1].STATE
CHAR
Status of message
“K”=coming
“G”=going
“Q”=acknowledged
2
EVENT[1].PVARS[1]
DWORD
Value of Process Variable 1 at the time
of the status change
6
EVENT[1].PVARS[2]
DWORD
Value of Process Variable 2 at the time
of the status change
10
EVENT[1].PVARS[3]
DWORD
Value of Process Variable 3 at the time
of the status change
14
EVENT[1].PVARS[4]
DWORD
Value of Process Variable 4 at the time
of the status change
18
EVENT[1].TIMESTAMP.YEAR
BYTE
Time stamp, year (BCD encoded)
19
EVENT[1].TIMESTAMP.MONTH
BYTE
Time stamp
Month (BCD encoded)
20
EVENT[1].TIMESTAMP.DAY
BYTE
Time stamp
Day (BCD encoded)
21
EVENT[1].TIMESTAMP.HOUR
BYTE
Time stamp
Hour (BCD encoded)
22
EVENT[1].TIMESTAMP.MINUTE
BYTE
Time stamp
Minute (BCD encoded)
23
EVENT[1].TIMESTAMP.SECOND
BYTE
Time stamp
Second (BCD encoded)
24 to 47
EVENT[2]...
BYTE
Second message
48 to 71
EVENT[3]...
BYTE
Second message
to
6120 to
6143
EVENT[256]...
BYTE
256th message
Содержание SIMATIC C7-613
Страница 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Страница 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Страница 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Страница 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Страница 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Страница 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Страница 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Страница 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...