A-12
C7-613 Control System
A5E00138934-03
Status, interrupts, diagnostics
Interrupts
•
Yes, if the corresponding channel is configured as an
interrupt input
•
For application of technological functions, refer to
“
S7-300 Programmable Controllers CPU31xC
Technological Functions
” manual.
Diagnostic functions
•
No diagnostics when operated as standard I/O
•
When using the technological functions, cf.
S7-300
Programmable Controller, CPU31xC Technological
Functions” manual
Data for selecting an encoder for standard DIs
Input voltage
•
Rated value
24 VDC
•
For signal “1”
15 V to 30 V
•
For signal “0”
-3 V to 5 V
Input current
•
For signal “1”
7 mA, typically
Delay of the standard inputs
•
Configurable
Yes (0.1/0.5/3/15 ms)
•
Rated value
3 ms
Input delay when using technological
functions
16
μ
s
Input characteristic
In accordance with IEC 1131, Type 1
Connection of 2-wire BEROs
Possible
•
Permissible quiescent current
Max. 1.5 mA