A-2
C7-613 Control System
A5E00138934-03
Safety
Standard references
DIN EN 61131-2 corresponds to IEC 61131-2
Protection against ingress of
solid foreign bodies and water
•
Front panel
•
Housing
IP65, to IEC 60529, NEMA 4X
IP20, to IEC 60529
Electromagnetic compatibility (EMC)
Emitted interference
Limit class
A
in accordance with EN55011
Cable-fed disturbances on DC
supply cables
±
2 kV (to IEC 61000-4-4; burst)
Surge measurements with additional protective elements:
±
1 kV (in accordance with IEC 61000-4-5;
μ
s-pulse/cable to cable)
±
2 kV (in accordance with IEC 61000-4-5;
μ
s-pulse/cable to ground)
Noise immunity on signal cables
±
2 kV (to IEC 61000-4-4; burst)
Interference immunity from static
discharges
±
6 kV, contact discharge
(in accordance with IEC 61000-4-2;
ESD)
±
8 kV, air discharge
(in accordance with IEC 61000-4-2;
ESD)
Radio frequency-proof
10 V/m,
with 80% amplitude modulation at 1 kHz,
10 kHz to 80 MHz (in accordance with IEC 61000-4-6)
10 V/m,
with 80% amplitude modulation at 1 kHz,
80 kHz to 1 GHz (in accordance with IEC 61000-4-3)
10 V/m,
pulse-modulated 50 % ED at 900 MHz and
1.89 GHz (in accordance with IEC61000-4-3)
Climatic conditions
Temperature
•
Operation
Tested in accordance with IEC 60068-2-1 and IEC 60068-2-2:
0
°
C to +40
°
C
for horizontal mounting
0
°
C to +45
°
C for
45
°
mounting
0
°
C to +50
°
C
for vertical mounting
Note:
•
When the device is in a horizontal mounting position, display
readability is limited.
•
At temperatures < 10
°
C, rapidly changing displays do not appear
correctly.
•
Storage/transport
-20
°
C to +70
°
C
Relative humidity
•
Operation
•
Storage/transport
Tested in accordance with IEC 60068-2-3
5% to 95% at 25
°
C (no condensation)
5% to 95% at 25
°
C (no condensation)
Air pressure
•
Operation
•
Storage/transport
1080 to 795 hPa (corresponds with -1000 m to +2000 m)
1080 to 660 hPa (corresponds with -1000 m to +3500 m)
Содержание SIMATIC C7-613
Страница 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Страница 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Страница 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Страница 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Страница 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Страница 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Страница 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Страница 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...