Error Information for HMI FBs and System Messages
B-11
C7-613 Control System
A5E00138934-03
B.2
System Messages
Introduction
This chapter presents system messages, including when system messages occur
and how the cause of the error can be removed.
Note
So long as there are no data blocks with configuration data in the C7-613 or the
integrated HMI module, system languages are displayed in English.
System Messages
System Message
Cause
Remedy
$ 000
V.... (Version)
SIMATIC C7-613
Startup
The integrated HMI
module of C7-613 is being
initialized.
This is a status message that provides
information about the function that is currently
being performed. The integrated HMI module of
the C7-613 is undergoing a cold restart. No
additional action is required.
$ 001
Parameters have not
been assigned to the
C7-613.
There are no data blocks
with configuration data.
Load the data blocks with the configuration data
to the MMC, and reinitiate parameter
assignment for the integrated HMI module.
Since a valid parameter assignment does not
yet exist, a STOP to RUN transition is sufficient.
A parameter assignment
error was detected during
the transfer.
Evaluate the “RETVAL” error information and
the “ADDINFO” status information of the
“HMI API” FB. Eliminate the parameter
assignment error, and reinitiate a parameter
assignment for the integrated HMI module.
Since a valid parameter assignment does not
yet exist, a STOP to RUN transition is sufficient.
$ 002
Parameter assignment is
underway
(Note: You can edit the
text for this system
message freely in every
language selected by you
by using the configuration
interface.)
The parameter
assignment operation is
not yet completed.
The DBs with the configuration data are being
loaded from the MMC to the internal memory of
the integrated HMI module. This always occurs
following a power ON or general reset, or when
the “Reload application” or “Swap languages”
system function is applied. Wait until the
parameter assignment is completed. Parameter
assignment can last several minutes depending
on the size of the project
(refer to Section 4.2).
The integrated HMI module of the C7-613 can
also be configured during operation, if an
internal error occurs in the integrated HMI
module or during basic HMI functions.
HMI functions are not possible during
parameter assignment. Incoming messages are
delayed.
Содержание SIMATIC C7-613
Страница 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Страница 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Страница 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Страница 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Страница 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Страница 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Страница 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Страница 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...