Technical data
A-13
C7-613 Control System
A5E00138934-03
Digital outputs
Note
Technological functions utilize fast digital outputs. These outputs must only be
connected to resistive loads.
Number
Number of outputs
16
•
Of those are high-speed outputs
4
Cable length
•
Unshielded
Maximum 600 m
•
Shielded
Maximum 1,000 m (109 yd.)
Voltage, currents, potentials
Rated load voltage L+
24 VDC
•
Polarity reversal protection
Yes
Accumulated output current
(per group)
•
Vertical mounting position
– Up to 40
°
C
Max. 3.0 A
– Up to 50
°
C
Max. 2.0 A
•
45
°
mounting position
– Up to 45
°
C
Max. 2.0 A
•
Horizontal mounting position
– Up to 40
°
C
Max. 2.0 A
Galvanic isolation
•
Between channels and P-bus
Yes
•
Between channels
Yes
– In groups of
8
Permissible potential difference
•
Between different circuits
75 VDC/60 VAC
Insulation tested at
500 V DC
Current consumption from load voltage L+
Max. 20 mA per group
Содержание SIMATIC C7-613