A-20
C7-613 Control System
A5E00138934-03
Data for selecting an actuator
Output range (rated values)
•
Voltage
±
10 V
0 V to 10 V
•
Current
±
20 mA
0 mA to 20 mA
4 mA to 20 mA
Load resistance
(in the rated range of the output)
•
Voltage outputs
– ohmic load
Minimum 1 k
Ω
– Capacitive load
Maximum 0.1
μ
F
•
Current outputs
– ohmic load
Maximum 300
Ω
– inductive load
max. 0.1 mH
Voltage output
•
Short-circuit protection
Yes
•
Short-circuit current
55 mA, typically
Current output
•
No-load voltage
Typically 17 V
Destruction limit for externally applied
voltages / currents
•
Output voltage to M
ANA
Maximum 16 V continuous;
•
Current
Max. 50 mA continuous
Connection of actuators
•
For voltage output
– 2-wire connection
Possible, without cable resistance compensation
– 4-wire connection (measuring line)
Not possible
•
For current output
– 2-wire connection
Possible