A-18
C7-613 Control System
A5E00138934-03
Analog outputs
Number
Number of outputs
2
Cable length
Shielded cable length
Maximum 200 m (109 yd.)
Voltage, currents, potentials
Rated load voltage L+
24 VDC
•
Polarity reversal protection
Yes
Galvanic isolation
•
Between channels and P-bus
Yes
•
Between channels
No
Permissible potential difference
•
Between outputs and M
ANA
(V
CM
)
8.0 V DC
•
between M
ANA
and M
internal
(V
ISO
)
75 VDC/60 VAC
Insulation tested at
500 V DC
Analog value generation
Resolution (incl. overshoot range)
11 bits + sign bit
Conversion time (per channel)
1 ms
Settling time
•
For resistive load
0.6 ms
•
For capacitive load
1.0 ms
•
For inductive load
0.5 ms