Technical data
A-11
C7-613 Control System
A5E00138934-03
A.4
Technical Specifications for Integrated I/O
Digital inputs
Number
Number of inputs
24
•
inputs usable for technological functions
12
Cable length
•
Unshielded
– For standard DI
– Technological functions
Maximum 600 m
non-shielded cables not allowed
•
Shielded
– For standard DI
– Technological functions
Maximum 1,000 m (109 yd.)
Max. 50 m
Voltage, currents, potentials
Rated load voltage L+
24 VDC
•
Polarity reversal protection
Yes
Number of inputs that can be triggered
simultaneously
•
Vertical mounting position
– Up to 40
°
C
18
– Up to 50
°
C
12
•
45
°
mounting position
– Up to 45
°
C
12
•
Horizontal mounting position
– Up to 40
°
C
12
Galvanic isolation
•
Between channels and P-bus
Yes
•
Between channels
No
Permissible potential difference
•
Between different circuits
75 VDC/60 VAC
Insulation tested at
500 V DC
Power consumption from load voltage L+
(no-load)
Max. 70 mA
Содержание SIMATIC C7-613
Страница 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Страница 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Страница 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Страница 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Страница 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Страница 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Страница 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Страница 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...