5.7.2.4
Parameterization of Energy Pulses via Parameterization Software
To parameterize energy impulses via parameterization software (refer also to chapter 5.7.1),
proceed as follows:
1. Select the
Measured value
to be counted.
2. 2.Select the
Test point
for the energy measurement.
3. Select the
Pulse
length for the signal.
4. Calculate the smallest energy increase per pulse. Use the description in chapter 5.7.2.3 to
calculate the minimum value.
You can use the
Help
field in the dialog window for the calculation. For this purpose, enter
the connected consumer power in the
kW in total
field. Then switch over to another field of
this dialog window to update the display. The smallest possible power increase per pulse for
the connected consumer power you have entered is displayed in the
Help
field under
Input
can be in range
.
5. For the value entered in the field
Energy increase per pulse
, a pulse will be applied to the
selected output each time when the given value will be reached
Note
Smallest pulse length = 50 ms.
Note
When you open the dialog for the first time, default values will be displayed. These values are
derived from the connection type (single-phase, three-phase or four-phase circuit), the voltage
and current range and the transformer ratios
The default values are only valid when you open the dialog for the first time!