8
8.1 SICAM P 7KG7750
137
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
Analog inputs (Connector Block A, optional)
Analog outputs (Connector Block A, optional)
Relay outputs (Connector Block A, optional)
8.1.1.3
Communication Interface (Connector J)
Recommended termination of the RS485 Interface see chapter 1.6.3.
Measuring range
DC 0 mA to 20 mA
Input range
DC 0 mA to 24 mA
Input resistance
50
Ω
± 0.1 %
Accuracy
0.5 % of the measuring range limit
Output current
DC 0 mA to 20 mA
Output range
DC 0 mA to 24 mA
Max. load resistance
250
Ω
Accuracy
0.2 % (typical); max. 0.5 % of the nomi-
nal value
Max. switching voltage
AC 150 V; DC 150 V
Max. permanent current
AC 5 A; DC 5 A
Min. permanent current
1 mA at DC 5 V
Rating (resistive)
AC 5 A/150 V or DC 5 A/30 V
Max. response time
10 ms
Max. release time
7 ms
Connection
Terminal side, 9-pin D-sub socket
RS485
Protocol PROFIBUS DP-V1
Baud rate
9600 bit/s to 12 Mbit/s
Protocol IEC 60870-5-103
Baud rate
9600 bit/s, 19 200 bit/s, 38 400 bit/s
Protocol Modbus RTU/ASCII
Baud rate
300 bit/s, 600 bit/s, 1200 bit/s,
2400 bit/s, 4800 bit/s, 9600 bit/s,
19 200 bit/s, 38 400 bit/s, 57 600 bit/s,
115 200 bit/s