5.9 Memory Management
111
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
5. Also, you must indicate the
Averaging interval
(5 s, 10 s, 15 s, 30 s, 1 min, 5 min, 10 min,
15 min, 30 min, 60 min) and the
Storage interval
(5 s, 10 s, 15 s, 30 s, 1 min, 5 min, 10 min,
15 min, 30 min, 60 min). These parameters set the number of measured values to be used
for mean value calculation and the interval for saving the values.
5.9.3
Power Values
In this dialog window you can specify the settings for power recording.
Proceed as follows:
1. Select up to eight
Measured values
and
Test points
.
2. Select a
Date
or one of the six
Limit value groups
as
Start selector
for the power recording.
It is possible to combine Date and Limit value group as start selectors. The first of the two
criteria fulfilled, will launch the recording.
3. When entering a date as
Start selector
, you must indicate a year between 2000 and 2060.
Note
If you have entered a past start date, SICAM P will initiate mean value recording immediately
after the setting. Manual start is not activated by configuration but can be initiated at any time.
Note
If the device provides additional analog inputs (optional), you can record external measurement
signals.