5.9 Memory Management
115
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
5.9.5
Parameterization Oscilloscope
The oscilloscope can be set via this dialog window.
Proceed as follows:
1. Select up to three
measured quantities
: An oscilloscope recording is started via the
selected
limit value group
(groups 1 to 6 are allowed).
2. Also, you must determine whether to record
Instantaneous
values or
RMS values
.
3. The
Ring buffer
mode allows you to select, if the oldest values will be overwritten (=
Yes
) or
not (=
No
) when the capacity of the associated memory area is exhausted.
4. Indicate the
Storage duration
in seconds.
Note
When changing the value type (instantaneous or RMS), the present selection will be reset since
the two types of measured values have different value ranges.
Note
In the submenu
Memory management
→
Splitting
you can see what storage time corresponds
to the indicated percentage for oscilloscope.