
4
4.4 Basic Settings
73
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
Range for Modbus protocol
•
from:
min. -32767
•
to:
max. 32767
Calculation:
Example:
from:
0
to:
1000
selected range:
4-20 mA
transmitted AO value: 500
Current range
•
0-20 mA
•
4-20 mA
AO
fern
from
–
AO
real
AO
min
–
-----------------------------------------
to
from
–
range
max
min
–
(
)
--------------------------------------
=
500
0
–
AO
real
4
–
---------------------------
1000
0
–
20
4
–
---------------------
12mA
=
=