8
8.1 SICAM P 7KG7750
136
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
Inputs for Alternating Current Measurements (Connector Block E)
Binary Outputs (Connector Block G)
Binary Inputs (Connector Block A, optional)
Input alternating currents
Rated input current range
1 A
5 A
Max. input current
2 x rated input alternating current
Power consumption per input
at 1 A
83
μ
VA
at 5 A
2.1 mVA
Further information about the current measuring inputs
Max. rated input voltage
150 V
Measuring error (with calibration) at 23 °C ± 1 °C
50 Hz or 60 Hz
Typically ±0.1 % at reference conditions
Thermal stability
10 A continuous
100 A for max. 1 s
Maximum contact voltage
Alternating voltage
230 V
Direct voltage
250 V
Maximum currents
Maximum continuous contact current
100 mA
Maximum pulse current for 0.1 s
300 mA
Further information about the binary outputs
Internal impedance
35
Ω
Admissible switching frequency
10 Hz
Number of switching cycles
Unlimited
Max. input voltage
DC 150 V
Current consumption for high level
DC 1,8 mA
Low level
≤
10 V
High level
≥
19 V
Signal delay
max. 3 ms