Connection
6.2 Connecting the main circuit
Manual, 08/2017, L1V30368969104A-02
43
Requirements
●
Power supply is switched off
●
Transfer switching equipment is in the "Manual" position
Procedure
Figure 6-12 Mounting bridging bars for current ratings 250 A to 630 A
Current rating
250 A
M10 x 20 mm
17
20 ... 26
400 A
M10 x 25 mm
630 A
M12 x 30 mm
19
40 ... 45
1.
Position the bridging bar on the connecting terminal.
2.
Fix the first half of the bridging bar to the connecting terminal with the bolt and washer.
3.
Fix the second half of the bridging bar to the connecting terminal with the bolt and
washer.
Note
The two halves of the bridging bar must come into contact completely before work step 4.
4.
Connect the two parts of the bridging bar with 1 bolt, 2 washers and 1 nut in accordance
with the figure.
Содержание SENTRON
Страница 1: ......
Страница 2: ......
Страница 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Страница 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Страница 20: ...Product information 3 1 Product description 20 Manual 08 2017 L1V30368969104A 02 3KC8 2000 A 2500 A 3200 A ...
Страница 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Страница 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Страница 138: ...Operation 7 4 Automatic mode programming of the electronic module 3KC8 only 138 Manual 08 2017 L1V30368969104A 02 ...
Страница 144: ...Commissioning 8 2 Commissioning the 3KC8 transfer switching equipment 144 Manual 08 2017 L1V30368969104A 02 ...
Страница 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Страница 182: ...Service and maintenance 10 2 Regular service and maintenance 182 Manual 08 2017 L1V30368969104A 02 ...
Страница 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...