Connection
6.3 Connecting the control circuit
Manual, 08/2017, L1V30368969104A-02
85
Requirements
●
Power supply is switched off
Procedure
1.
Disassemble the motor operator in accordance with the section titled Motor operator
(Page 170).
2.
Place the auxiliary switch at the corresponding position and secure it to the transfer
switching equipment.
–
When installing 1 auxiliary switch use 4 short bolts M3 x 18 mm.
–
When installing 2 auxiliary switches use 4 long bolts M3 x 30 mm.
Figure 6-68 Installing auxiliary switches 800 A to 1600 A
3.
Lay the cable of the auxiliary switch around the transfer switching equipment in
accordance with the figure.
Figure 6-69 Arranging auxiliary switch cables 800 A to 1600 A
Содержание SENTRON
Страница 1: ......
Страница 2: ......
Страница 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Страница 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Страница 20: ...Product information 3 1 Product description 20 Manual 08 2017 L1V30368969104A 02 3KC8 2000 A 2500 A 3200 A ...
Страница 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Страница 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Страница 138: ...Operation 7 4 Automatic mode programming of the electronic module 3KC8 only 138 Manual 08 2017 L1V30368969104A 02 ...
Страница 144: ...Commissioning 8 2 Commissioning the 3KC8 transfer switching equipment 144 Manual 08 2017 L1V30368969104A 02 ...
Страница 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Страница 182: ...Service and maintenance 10 2 Regular service and maintenance 182 Manual 08 2017 L1V30368969104A 02 ...
Страница 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...