Connection
6.3 Connecting the control circuit
74
Manual, 08/2017, L1V30368969104A-02
Requirements
●
Main circuit is disconnected
Procedure
1.
Check whether the switch on the transfer switching equipment is in the "Manual" position.
Figure 6-51 Set the switch to the "Manual" position
2.
Connect the supply lines with the connector for the control inputs.
For 3KC8 only
Figure 6-52 Connecting supply cables
3.
Connect the supply lines with the connector for the outputs of the motor operator. You
can see the designations of the inputs and outputs in the figure.
4.
Tighten the contacts with a screwdriver.
5.
Insert the connector in the terminal of the control inputs.
6.
Insert the connector in the terminal of the outputs.
Содержание SENTRON
Страница 1: ......
Страница 2: ......
Страница 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Страница 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Страница 20: ...Product information 3 1 Product description 20 Manual 08 2017 L1V30368969104A 02 3KC8 2000 A 2500 A 3200 A ...
Страница 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Страница 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Страница 138: ...Operation 7 4 Automatic mode programming of the electronic module 3KC8 only 138 Manual 08 2017 L1V30368969104A 02 ...
Страница 144: ...Commissioning 8 2 Commissioning the 3KC8 transfer switching equipment 144 Manual 08 2017 L1V30368969104A 02 ...
Страница 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Страница 182: ...Service and maintenance 10 2 Regular service and maintenance 182 Manual 08 2017 L1V30368969104A 02 ...
Страница 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...