Applications
13.2 Transfer between two sources with two outgoing loads
Manual, 08/2017, L1V30368969104A-02
207
13.2
Transfer between two sources with two outgoing loads
Transfer with T1 (kVA) > T2/G (kVA)
With this application, the power of source I is greater than that of source II
(T1 (kVA) > T2/G (kVA). One generator and one transformer are usually used for this.
However, with this application, the 3KC8 transfer switching equipment can also switch
between two transformers. The load is divided into a critical and non-critical load here.
Figure 13-2 Transfer T1 (kVA) > T2/G (kVA)
T1
T2/G
Switching state
of the
transfer switching
equipment
Non-critical load
Critical load
0
0
x
OFF
OFF
1
0
P1
ON
ON
0
1
P2
OFF
ON
1
1
P1
ON
ON
Содержание SENTRON
Страница 1: ......
Страница 2: ......
Страница 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Страница 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Страница 20: ...Product information 3 1 Product description 20 Manual 08 2017 L1V30368969104A 02 3KC8 2000 A 2500 A 3200 A ...
Страница 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Страница 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Страница 138: ...Operation 7 4 Automatic mode programming of the electronic module 3KC8 only 138 Manual 08 2017 L1V30368969104A 02 ...
Страница 144: ...Commissioning 8 2 Commissioning the 3KC8 transfer switching equipment 144 Manual 08 2017 L1V30368969104A 02 ...
Страница 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Страница 182: ...Service and maintenance 10 2 Regular service and maintenance 182 Manual 08 2017 L1V30368969104A 02 ...
Страница 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...