Connection
6.2 Connecting the main circuit
Manual, 08/2017, L1V30368969104A-02
67
Connecting versions 7 and 8
Requirements
●
Main circuit is disconnected
●
Transfer switching equipment is in the "Manual" position
●
Copper bar connection kit is mounted
Procedure
The bolt set required for mounting is not included with the transfer switch. You can find the
bolt set requirements in the following table:
Version
Bolt
Washer
Nut
7 (horizontal)
2000 … 2500 A
10 x H M12-55 6.8
20 x
10 x
8 (horizontal)
3200 A
10 x H M12-65 6.8
20 x
10 x
1.
Mount the busbar with 10 bolts, 20 washers and 10 nuts on the transfer switching
equipment.
Figure 6-42 Connecting versions 7 and 8
2.
Connect the mounted transfer switching equipment to the power supply systems.
–
For the 3-pole type with 3 x the above listed bolt set.
–
For the 4-pole type with 4 x the above listed bolt set.
Содержание SENTRON
Страница 1: ......
Страница 2: ......
Страница 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Страница 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Страница 20: ...Product information 3 1 Product description 20 Manual 08 2017 L1V30368969104A 02 3KC8 2000 A 2500 A 3200 A ...
Страница 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Страница 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Страница 138: ...Operation 7 4 Automatic mode programming of the electronic module 3KC8 only 138 Manual 08 2017 L1V30368969104A 02 ...
Страница 144: ...Commissioning 8 2 Commissioning the 3KC8 transfer switching equipment 144 Manual 08 2017 L1V30368969104A 02 ...
Страница 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Страница 182: ...Service and maintenance 10 2 Regular service and maintenance 182 Manual 08 2017 L1V30368969104A 02 ...
Страница 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...