Accessories
9.1 Terminal covers
Manual, 08/2017, L1V30368969104A-02
147
9.1.1
Mounting terminal covers
The following steps are necessary for fitting the terminal covers on the 3KC4 and 3KC8
transfer switching equipment of current ratings 250 A to 630 A.
Note
If bridging bars are used, mount them first.
Requirements
●
Main circuit is disconnected
●
Transfer switching equipment is in the "Manual" position
●
Bridging bars are mounted (if used)
●
Accessories for the electronic module installed (3KC8 only)
Procedure
Figure 9-2
Mounting terminal covers
1.
Connect the terminal covers with each other depending on the number of poles.
2.
Place the connected terminal covers in the draw-out assembly of the transfer switching
equipment.
Note
When using bridging bars, only the terminal cover for the front may be used.
Содержание SENTRON
Страница 1: ......
Страница 2: ......
Страница 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Страница 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Страница 20: ...Product information 3 1 Product description 20 Manual 08 2017 L1V30368969104A 02 3KC8 2000 A 2500 A 3200 A ...
Страница 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Страница 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Страница 138: ...Operation 7 4 Automatic mode programming of the electronic module 3KC8 only 138 Manual 08 2017 L1V30368969104A 02 ...
Страница 144: ...Commissioning 8 2 Commissioning the 3KC8 transfer switching equipment 144 Manual 08 2017 L1V30368969104A 02 ...
Страница 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Страница 182: ...Service and maintenance 10 2 Regular service and maintenance 182 Manual 08 2017 L1V30368969104A 02 ...
Страница 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...