Connection
6.1 Network types
34
Manual, 08/2017, L1V30368969104A-02
6.1.2.1
Circuit diagram for the 3KC4 transfer switching equipment - 3-pole transfer switching
equipment
Figure 6-3
Three-phase 3-wire network without neutral for the 3KC4 transfer switching equipment
F1
2 x 3NW6002-1
1 x 3NW7023
2 A, gG
F2
1 x 3NW6004-1
1 x 3NW7013
4 A, gG
With this arrangement there is no neutral conductor available. For this reason, the following
optional accessories can/must be used for establishing this network:
●
2 x autotransformer 3KC9824-1. For information, see the section titled Installing and
connecting an autotransformer (400 V / 230 V) (Page 79).
●
1 x dual power supply 3KC9625-1. For information, see the section titled Mounting and
connecting the dual power supply (DPS) (Page 77).
Note
The F1 fuses must be installed as closely as possible to the tap.
The F2 fuses must be fitted as closely as possible to the output of the autotransformer.
Содержание SENTRON
Страница 1: ......
Страница 2: ......
Страница 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Страница 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Страница 20: ...Product information 3 1 Product description 20 Manual 08 2017 L1V30368969104A 02 3KC8 2000 A 2500 A 3200 A ...
Страница 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Страница 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Страница 138: ...Operation 7 4 Automatic mode programming of the electronic module 3KC8 only 138 Manual 08 2017 L1V30368969104A 02 ...
Страница 144: ...Commissioning 8 2 Commissioning the 3KC8 transfer switching equipment 144 Manual 08 2017 L1V30368969104A 02 ...
Страница 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Страница 182: ...Service and maintenance 10 2 Regular service and maintenance 182 Manual 08 2017 L1V30368969104A 02 ...
Страница 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...