6.3 Parameterizing the device
PAC2200CLP
66
Equipment Manual, 06/2021, L1V30820585B-02
Selection
Range
Factory setting
SNTP
Protocol is used for transmitting and synchronizing the
time.
•
OFF:
SNTP function not active
•
ACTIVE:
The device automatically requests the time from
the NTP server.
•
BCST client:
The device receives time telegrams
which are sent from an NTP server.
OFF
IP
(only when SNTP is
activated)
If an SNTP IP address is configured, only data from this
IP address is accepted.
0.0.0.0
SNTP STATUS OK
(only when SNTP is
activated)
•
ACTIVE:
SNTP server is available
•
NOT ACTIVE:
SNTP server is unavailable
–
"Integrated I/O" parameter
"Digital input" parameter
The following functions can be assigned to the "Digital input" parameter:
•
Tariff switching for two-tariff, active energy, and reactive energy counters.
Selection
Range
Factory setting
ACTION
•
NONE:
Input is deactivated.
•
PULSE INPUT:
Counting of input pulses
•
HT/LT SWITCHING
:
Switching between tariffs. Low tariff if input active.
•
DISPLAY:
Backlighting. Backlighting ON, if input is active.
NONE
UNIT
The "UNIT" property is only visible if "PULSE INPUT" is
set for the "ACTION".
Countable unit with pulse counting:
•
Active energy (kWh)
•
Reactive energy (kvarh)
—
PULSES PER UNIT
The "PULSES PER UNIT" property is only visible if "PULSE
INPUT" is set for the "ACTION".
Range: 1 to 4000
1
PRO
(input pulse divider)*
The "PULSES PER UNIT" property is only visible if "PULSE
INPUT" is set for the "ACTION".
Range: 1; 10; 100; 1000
1
Содержание SENTRON PAC2200CLP
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 50: ...Connection 4 4 Connecting the communication cable PAC2200CLP 48 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 60: ...Operation 5 4 Protection against manipulation PAC2200CLP 58 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 86: ...Technical specifications 8 1 Technical specifications PAC2200CLP 84 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 94: ...Dimension drawings 9 1 Dimensional drawings PAC2200CLP 92 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 129: ......
Страница 130: ......