Appendix
A.1 Modbus TCP
PAC2200CLP
120
Equipment Manual, 06/2021, L1V30820585B-02
Description
Number
Can be used on "
Data Log Identifier"
Measuring channel 2 (average values and
cumulated values)
0x62
0x00
Measuring channels 1 und 2 (average values)
0x63
0x00
Measuring channel 1 (average values)
0x64
0x00
Measuring channel 2 (average values)
0x65
0x00
Measuring channels 1 und 2 (cumulated
values)
0x66
0x00
Measuring channel 1 (cumulated values)
0x67
0x00
Measuring channel 2 (cumulated values)
0x68
0x00
Measuring channels 1 and 2 (energy quanti-
ty)
0x69
0x00, 0x04, 0x05, 0x06
Measuring channel 1 (energy quantity)
0x6A
0x00, 0x04, 0x05, 0x06
Measuring channel 2 (energy quantity)
0x6B
0x00, 0x04, 0x05, 0x06
Measuring channels 1 and 2 (energy quanti-
ty), in addition 4 counter readings (import T1,
import T2, export T1, export T2)
0x6C
0x00, 0x04, 0x05, 0x06
Measuring channels 1 and 2 (energy quanti-
ty), in addition 2 counter readings (total im-
port T1+T2, total export T1+T2)
0x6D
0x00, 0x04, 0x05, 0x06
4 counter readings (import T1 and T2, export
T1 and T2)
0x70
0x00, 0x04, 0x05, 0x06
2 counter readings (import T1, export T1)
0x71
0x00, 0x04, 0x05, 0x06
2 counter readings (import T2, export T2)
0x72
0x00, 0x04, 0x05, 0x06
Definition "Advanced Data Identifier"
The "advanced data identifier" has a length of 5 bytes. It consists of an object ID (4 bytes,
format "unsigned long" big endian) and the number (1 byte) of data records required in the
response frame.
Every data record of a historical data memory in the PAC device can be addressed by this
object ID (OID) which is unique in the device. A special entry (or a number of entries which
are inserted in the frame one after the other) can be read.
The highest OID in existence is available for every data memory in associated Modbus
registers (see table "Data memory and associated Modbus registers").
If OID 0x00000000 is requested, the PMD returns the oldest valid OID with the associated
data record. If a non-existent OID (other than 0) is requested, the PAC device returns the
Modbus exception code 0x04. A syntax error in the Modbus frame also results in a Modbus
exception response.
Data memory und associated Modbus registers
Description "Data Log
Identifier"
Modbus register of the
highest OID in exist-
ence
Data format
Length
Load profile memory
0x00E4
Unsigned long
2 registers
Daily profile memory
0x010A
Unsigned long
2 registers
Monthly profile
memory
0x010C
Unsigned long
2 registers
Содержание SENTRON PAC2200CLP
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 50: ...Connection 4 4 Connecting the communication cable PAC2200CLP 48 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 60: ...Operation 5 4 Protection against manipulation PAC2200CLP 58 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 86: ...Technical specifications 8 1 Technical specifications PAC2200CLP 84 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 94: ...Dimension drawings 9 1 Dimensional drawings PAC2200CLP 92 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 129: ......
Страница 130: ......