6.2
Industrial Ethernet
6.2.1
Industrial Ethernet
Ethernet ports
The attachment to Industrial Ethernet uses M12 connector technology with MDI-X assignment.
Fast Ethernet
For connection to Industrial Ethernet at 10/100 Mbps, the device has the following M12
interfaces: D-coded, 4-pin, female.
3[[
Pin number
Assignment
1
TD+
2
RD+
3
TD-
4
RD-
Gigabit Ethernet
For connection to Industrial Ethernet at 10/100/1000 Mbps, the device has the following M12
interfaces: X-coded, 8-pin, female.
3[[
Connecting up
6.2 Industrial Ethernet
SCALANCE XP-200
56
Operating Instructions, 03/2021, C79000-G8976-C428-08