Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Application examples
15.07.2002
8.13
Plant types RVA47.320 - no. 67
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve.
Control of the pump heating circuit by the RVA47.320 based on the heat demand signal
received via input H1.
4
1
2
3
B10
23
79
S3
6
B70
Type of unit
BMU 1
BMU 2
BMU 3
BMU 4
RVA47.320
Display of plant type
67
Heating curve (line 17)
--- (inactive) or 2.5...40
Pump function Q1 (line 95)
5 (pump H1)
Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
The heat demand signal for the pump heating circuit is generated via input H1.
In addition, the controller itself can generate a weather-compensated flow temperature
(setting the heating curve to a valid value).
When there is only a heat demand signal from the d.h.w. storage tank (heating circuits
do not currently call for heat), the boiler put into operation is only that to which the
storage tank is hydraulically connected. The other boilers of the cascade will not be
released.
L
N
Q1
F1
N1
Q3
B3
B9
B70
B70
M
L
N
23
79A
33
MB
LPB
MD
A6 / BMU
PPS
DB
B10
B
M
H1
B10
B
M
B9
B
M
A6
B
M
H1
The d.h.w. sensor (B3) is connected directly to BMU 1.
For a detailed legend, refer to page 158.
Note
Hydraulic circuit
Important
Notes
Electrical connections
Note
Legend