15/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Handling
15.07.2002
2.1.4 Required
cut-out
The controller’s mounting dimensions are 91 x 91 mm.
Due to the dimensions of the front, however, the standard spacing is 96 mm.
The mechanical mounting facility allows the controller to be fitted in front panels having
a thickness of 2 to 10 mm.
The mechanical mounting facility makes
it possible to arrange several controllers
in a row in one cut-out. In that case, it is
merely necessary to have a wider panel
cutout.
2379Z15
2.1.5 Orientation
To avoid overtemperatures inside the
controller, the inclination may be no
more than 30° and there must be a
clearance of at least 10 mm on all sides
of the unit.
This allows the controller to emit the
heat generated during operation.
10
mm
m
a
x
.
3
0
°
2371Z16
10
mm
Dimensions of cut-out
96
2...10
92
+0
.8
-0
92
+0.8
-0
96
92
+0.8
-0
23
71
M
02
188
96
Use of several
controllers