Plant types RVA47.320 - no. 65
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs. Control of the pump
heating circuit by the RVA47.320 based on the heat demand signal received via input
H1.
4
1
2
3
B10
B70
23
79
S
34
Type of unit
BMU 1
BMU 2
BMU 3
BMU 4
RVA47.320
Display of plant type
65
Heating curve (line 17)
--- (inactive) or 2.5...40
Pump function Q1 (line 95)
5 (pump H1)
Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
The heat demand signal for the pump heating circuit is generated via input H1.
In addition, the controller itself can generate a weather-compensated flow temperature
(setting the heating curve to a valid value).