Description of the enduser settings
15.07.2002
Individual days
The setting of the switching times from operating line 6 through 11 is entered
only
for
the individual day selected here.
Tip
First, choose the 7-day block (1-7) to enter the switching times that apply to the
majority of days; then, select the individual days (1...7) to make the required
adjustments.
0 2 4 6 8 10 12 14 16 18 20 22 24 h
Sa
Mo
Di
Mi
Do
Fr
So
23
7
3Z
12
3.10 Switching
times
With this setting, you determine the switching times for space heating. At these
switching times, the temperature setpoints of the heating circuit change.
The heating program thus set becomes active when selecting automatic mode
.
1. Press the line selection buttons to select line 6 to 11.
2. Press the + / – buttons to set the switching time on each line.
Setting range
Unit
Factory setting
- -:- -...24:00
h : min
See "Program overview"
below
First, select the weekday (operating line 5) for which the switching times shall be
entered!
The controller then makes a check to ensure the entries have been made in the correct
order.
At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.
Entry of
1...7
Example:
Description
Setting
• • •
!
Important
Note
Effect