156/166
Siemens Building Technologies
Basic Documentation RVA47.320
CE1P2379E
HVAC Products
Application examples
15.07.2002
8.12
Plant types RVA47.320 - no. 66
The plant type no. is identical with the number displayed on line 53.
Control of a single BMU or cascade control of up to four BMUs.
D.h.w. heating with charging pump through the RVA47.320.
Control of the pump heating circuit by the RVA47.320 based on the heat demand signal
received via input H1.
4
1
2
3
B10
B70
23
79
S3
5
B3
Type of unit
BMU 1
BMU 2
BMU 3
BMU 4
RVA47.320
Display of plant type
66
Heating curve (line 17)
--- (inactive or 2.5...40
Pump function Q1 (line 95)
5 (pump H1)
Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
The heat demand signal for the pump heating circuit is generated via input H1.
In addition, the controller itself can generate a weather-compensated flow temperature
(setting the heating curve to a valid value).
L
N
Q1
F1
N1
Q3
B3
B3
B9
B7
B70
M
L
N
23
79A
31
MB
LPB
MD
A6 / BMU
PPS
DB
B10
B
M
B
M
H1
B10
B
M
B9
B
M
A6
B
M
H1
For a detailed legend, refer to page 158.
Note
Hydraulic circuit
Important
Electrical connections
Legend