1. Press the operating line selection buttons to select operating line 103.
2. Press the + / - buttons to set the minimum limitation of the flow temperature
setpoint.
Einst ellbereich
Unit
Factory setting
8...TVmax °C
8
TVmax
Maximum limitation of flow temperature setpoint (setting on operating line 104)
0 10 20 30 40 50 60 70 80 90 100
TV
max
min
akt
°C
237
9Z
09
TVw
TVw Current flow temperature setpoint
103
Minimum limitation of flow temperature setpoint
104
Maximum limitation of the flow temperature setpoint
The setting will make certain that the flow temperature setpoint will not fall below a
minimum level.
If the flow temperature setpoint demanded by the heating circuit reaches the minimum
limit and the outside temperature rises, the flow temperature setpoint will be maintained
at that limit, in other words, it will not be allowed to fall below it.
4.31 Maximum
limitation
of the flow temperature
setpoint
•
Prevents too high flow temperatures
Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
1. Press the operating line selection buttons to select operating line 104.
2. Press the + / - buttons to set the maximum limitation of the flow temperature
setpoint.
Setting range
Unit
Factory setting
TVmin...95 °C
80
Tvmin Minimum limitation of flow temperature setpoint (setting on operating line 103)
Setting
Effect
Limitation
Benefit
Description
Setting