Technical specifications
6.2 Specific technical data
Power Module PM330
96
Hardware Installation Manual, 12/2018, A5E32844552B AF
Table 6- 6
PM330, frame size HX, 3-phase 500 … 690 VAC, Part 2
Article No.
6SL3310-
1PG35-2AA0
Rated input current
- at 500 V, 45 °C
- at 600 V, 45 °C
- at 690 V, 45 °C
- at 500 V, 55 °C
- at 600 V, 55 °C
- at 690 V, 55 °C
537 A
517 A
499 A
456 A
440 A
425 A
Rated input current DCP/DCN
(for 2/3 of the inverter power)
- at 675 V
DC
, 45 °C
- at 810 V
DC
, 45 °C
- at 930 V
DC
, 45 °C
- at 675 V
DC
, 55 °C
- at 810 V
DC
, 55 °C
- at 930 V
DC
, 55 °C
439 A
423 A
409 A
373 A
360 A
347 A
Rated output current I
N
- at 500 V, 45 °C
- at 600 V, 45 °C
- at 690 V, 45 °C
- at 500 V, 55 °C
- at 600 V, 55 °C
- at 690 V, 55 °C
516 A
497 A
480 A
438 A
422 A
408 A
LO base load power
LO base load input current at 690 V
LO base load output current at 690 V
450 kW
489 A
470 A
HO base load power
HO base load input current at 690 V
HO base load output current at 690 V
400 kW
410 A
394 A
Fuse according to IEC
manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1436-2
(630 A/690 V)
Siemens AG
≤ 100 kA
> 8.5 kA
Fuse in compliance with UL
2)
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1436-2
(630 A/690 V)
Siemens AG
≤ 100 kA
> 8.5 kA
max. power loss, at I
N
, 45 °C, 690 V
7.716 kW
Required cooling air flow
360 l/s
Maximum connectable cross-section of the line,
motor and DC-link cable
4 x 240 mm
2
4 x 500 kcmil
Recommended cable cross-section for 500 V
- line cable
- motor cable
3 x 120 mm
2
3 x 95 mm²
Recommended cable cross-section for 690 V
- line cable
- motor cable
3 x 120 mm
2
3 x 95 mm²
Содержание PM330
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents Power Module PM330 6 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 20: ...Introduction Power Module PM330 18 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 146: ...Appendix A 6 Abbreviations Power Module PM330 144 Hardware Installation Manual 12 2018 A5E32844552B AF ...
Страница 149: ......
Страница 150: ......